Download - Aplisens SA
Transcript
B1 4 DTR.APC.APR.FROFIBUS.02(ENG) Appendix Ex.PROFIBUS 7. Basic requirements for cable used to connect the transmitter to the power supply and measurement circuit. Load resistance Load inductance Load capacity Rc 15/km to 150/km, Lc 0,4mH/km to 1mH/km, Cc 45nF/km to 200nF/km, It is recommend to use shielded cable for types as below: Technotronic-bus O2YS(St)CY 1x2x1,0/2,6 mm produced by Technokabel SINEC 6XV1 830-5AH10 produced by SiemensAG SINEC 6XV1 830-3BH10 produced by SiemensAG 3079A produced by BELDEN. It is recommend to connect cable shield with earthing terminal of transmitter casing. Earthing terminal of transmitter casing connect with mass circuit or earth. It is not permitted to repair or otherwise interfere with the transmitter’s electrical circuits in any way. Damage and possible repair may be assessed only by the manufacturer or another authorized party. i Additional information about Profibus-PA networks and FISCO models can be found on: EN-60079-27 - Electrical apparatus for explosive gas atmospheres - Part 27: Fieldbus intrinsically safe concept (FISCO) and fieldbus non-incendive concept (FNICO)