Download LACCD IT Design Standards
Transcript
Input Current Limit: LACCD IT Design Standards 2009 The input converter shall control and limit the input current draw from utility to 130% of the UPS output. During conditions where input current limit is active, the UPS shall be able to support 100% load, charge batteries at 10% of the UPS output rating, and provide voltage regulation with mains deviation of up to +22%/ -10% of the nominal input voltage. Redundancy: When installing systems in a parallel redundant (PR) configuration, the system shall include redundant input converters, each with semiconductor fusing, and logic controlled contactors to remove a failed module from the power bus. Battery management system: The UPS shall contain a battery management system with the following features: Battery Recharge: The battery management system shall provide a three-step charging process. These periods shall be recognized as constant current, constant voltage and rest. After recharging batteries to full capacity, UPS shall isolate the charging circuit from the battery. Continual float charging of the battery shall not be allowed, therefore reducing the possibility of positive grid corrosion, and increasing expected battery life. Battery Runtime Monitoring: The battery management system shall monitor battery and provide status to end user of battery run time via front panel, serial/network communications, or both. Run time calculations to be based on load demand and analysis of battery health. Battery Health Monitoring: UPS shall continuously monitor battery health and the UPS will provide warnings visually, audibly and/or via serial/network communications when battery capacity falls below 80% of original capacity. Battery testing may also be user initiated via the front panel or serial communications. Parallel connected systems shall independently monitor their battery voltage during discharge. Each system shall communicate with other systems on the parallel bus, sending information about current battery conditions (voltage). Each UPS shall be able to adjust output load based upon its own battery voltage, therefore systems with incorrectly connected, weak or failed batteries shall assume less load ensuring maximum runtime out of the connected battery. Adjusting output loading based on battery voltage shall not allow a UPS inverter to exceed more than 100% of its rated capacity. The battery charging circuit shall remain active when in any normal mode of operation or while in static bypass mode. Back-feed Protection: Each UPS shall provide a UL1778 approved back-feed protection scheme. Enterprise Data Center Design – Std 003-0909 Page 31