Download Panasonic FP0 Controller User`s Manual
Transcript
Optional Memory 2.2 FP0 Specifications 2.2.3 Input Specifications Item Description Insulation method optical coupler Rated input voltage 24 V DC Rated input current approx. 4.3 mA (at 24 V DC) Input impedance approx. 5.6 kΩ Operating voltage range 21.6 to 26.4 V DC Input points per common (*Note 1) C10RM, C10CRM, C10RS, C10CRS 6 points/common C14RM, C14CRM, C14RS, C14CRS 8 points/common C16T, C16CT, C16P, C16CP 8 points/common C32T, C32CT, C32P, C32CP T32CT, T32CP 16 points/common ON voltage/ON current 19.2 V or less/3 mA or less OFF voltage/OFF current 2.4 V or more/1 mA or more OFF ↔ ON Response time 50 µs or less (at X0, X1) (* Note 2) 100 µs or less (at X2 to X5) (* Note 2) (at 24 V DC and 25 °C/66 °F) 2 ms or less (at X6 to XF) ON ↔ OFF Operating mode indicator the same as above LED Notes 1) Either positive or negative polarity is possible for the input voltage supply. 2) X0 through X5 are inputs for the high-speed counter and have a fast response time. If used as normal inputs, we recommend inserting a timer in the ladder program as chattering and noise may be interpreted as an input signal. 2 − 14 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]