Closed-loop thyristor current control
5.1.1 Hardware configuration
The ITDC converter gating is inserted on a PM5 or PM6 processor and
screwed into place. The modules have a local expansion bus (LE bus) via
which signals and data are transferred.
O p e ra to r c o n tro l d e v ic e
COM1/2
PM5 / 6
ITDC
X5
X01
SC57
9pin
l = 5m
Ext.Vsyn.
20pin
diagnostics sig.
2 analog o/p's
serial
interface
(service)
SC12
(20pin)
l = 2m
SU11 2 AO
X6
4 dig. outputs
4 dig. inputs
1 incremental
encoder
X5
10pin
20pin
SC12
4 DO
SU11 4 DI
1 INC
X7
LE
bus
SITOR
interface
SC17.2
50pin
or
l = 2m
SC31.2
~3AC
SITOR set
PM 1.
ITxx
Interrupt : LE-I1
2.
ITxx
or
interface : SE20.2
LE-I3
ITDC + ITxx
ITxx + ITDC
M
Fig. 5-1
NOTE
T
Hardware configuration
2 ITDC modules cannot be used on a processor module. However,
combinations with other expansion modules is permitted (e.g. IT41)
The interface: SE20.2 implements the mechanical conversion and the
electrical isolation of the standard SITOR interface from the ITDC to a
6QG5x SITOR cabinet or another drive converter.
SITOR sets 6QG2x and 6QG3x differ in the way that the
current actual value is sensed, the conditioning of the zero crossover
signals and the phase-to-phase voltages.
If a 6QG2x or 6QG3x SITOR set is used with an optional field device
module (excitation option), then the FB FCS is required.
The gating unit has been released for operation with 50 Hz and 60 Hz
line supplies (e.g. for PM5); however, it also has automatic frequency
adaptation in the range from 10 to 530 Hz.
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
5-3