Download Start-Up and Service Instructions
Transcript
Table 6 — Powerflex 755 Fault Code Descriptions and Corrective Actions (cont) VFD FAULT CODE ON VFD HIST SCREEN 38 39 ICVC FAULT STATE 220 40 41 42 FAULT TYPE Phase U to Gnd Phase V to Gnd DESCRIPTION Check the wiring between the drive and the motor. Check motor for grounded phase. Check Motor terminals. d. Replace drive. Check the wiring between the drive and the motor. Check Motor terminals. Replace drive. GROUND FAULT Phase W to Gnd 246 43 Phase UV Short Phase VW Short CORRECTIVE ACTION GROUND FAULT Phase WU Short 44 206 Phase UNot 45 206 46 206 Phase VNot ToGnd GROUND FAULT (no LF2 equivalent) Phase WNot 55 NONE 61 62 206 206 Shear Pin 1 Shear Pin 2 The temperature sensor on the main control board detected excessive heat. See VFD Fault Code 15 See VFD Fault Code 15 64 206 Drive Overload Drive is overloaded 65 77 206 206 See VFD Fault Code 15 See VFD Fault Code 15 78 206 OW TrqLvlTimeout IR Volts Range FluxAmpsRef Rang Check that VFD refrigerant isolation valves are open.Check VFD refrigerant strainer See VFD Fault Code 15 See VFD Fault Code 15 Check for high entering water temperature or low condenser water flow. Check current settings in VFD_CONF screen. See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 79 206 Excessive Load 80 206 AutoTune Aborted Inverter Overtemp Motor did not come up to speed in the allotted time See VFD Fault Code 15 Ixo voltae calculated from motor nameplate data is too high. See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 87 206 IXo VoltageRange 91 93 94 95 96 97 206 206 206 206 206 206 Pri VelFdbk Loss HW Enable Check Alt VelFdbk Loss Aux VelFdbk Loss PositionFdbkLoss Auto Tach Switch 100 206 The checksum read from the board does not Parameter Chksum match the checksum calculated. 107 NONE 113 206 Tracking DataErr Internal data error. 124 141 142 143 144 145 206 206 206 206 206 206 App ID Changed Autn Enc Angle Autn Spd Rstrct Autotune CurReg Autotune Inertia Autotune Travel Application firmware changed. P78 [Encdrlss AngComp] is out of range See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 The main control board was moved to a different Replaced MCB-PB power structure. Data set to default values. 21 Downloaded from www.Manualslib.com manuals search engine Check the wiring between the drive and the motor. Check Motor terminals. Replace drive. Check that guide vanes are closed completely. Check for high entering water temperature or low condenser flow. Repeat Autotune See VFD Fault Code 15 Re-enter motor nameplate data in VFD_CONF screen. See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 Press ICVC reset. Check VFD_CONF parameters. Cycle power to the drive. Press ICVC reset. Check VFD_CONF parameters. Cycle power to the drive. Press ICVC reset. Cycle power to the drive Verify application version. See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15 See VFD Fault Code 15