1592015700 User manual iCHILL 200 D GB
dP 2
dP 3
dP4
dP5
Pr1
Pr2
Pr3
Parameter
CF 1
CF 2
CF 3
CF 4
CF 5
CF 6
CF 7
CF 8
CF 9
CF 10
CF 11
CF 12
CF 13
CF 14
r1.4
23/11/2009
Default read-out of the bottom display
0
Default display read-out configuration top / bottom
0= Configurable
1= Top display: Evaporator IN, Bottom display: Evaporator OUT
0
2= Top display: Condenser IN, Bottom display: Condenser OUT
3=Top display: temperature/Condensing pressure, Bottom Display:
evaporating pressure
Display read-out of the remote terminals
Top display default read-out of the remote terminal_1
0= the read-out depends on the paremeters dP01 – dP02 – dP03
0
1= the read-out shows the NTC probe of the remote panel.
Top display default read-out of the remote terminal_2
0= the read-out depends on the paremeters dP01 – dP02 – dP03
0
1= the read-out shows the NTC probe of the remote panel.
Password
0
Password
0
Password
0
Configuration
Description
min
Unit Model
Type of unit
0= Air / air Chiller
0
1= Air / water Chiller
2= Water / water Chiller
Heat pump
0= no
0
1= Yes
Not used
0
Compressors
Compressors number for circuit 1
1= 1
2= 2
0
3= 3
4= 4
Compressors number for circuit 2
0= 0
1= 1
0
2= 2
3= 3
Number of compressor parzialization
0= none
1= 1
0
2= 2
3= 3
Analog Inputs
Pressure or temperature analogue input functioning
0 = Temperature / pressure NTC – 4÷20 mA :
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 4÷20mA
transducers.
1 = Pressure control with 4÷20 mA:
To control the evaporating and condensing pressures it is necessary a
0
4÷20mA transducer.
2 = Temperature / pressure NTC – 0÷5Vdc:
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers.
3 = Pressure control with 0÷5Vdc:
To control the evaporating and condensing pressures it is necessary a
ratiometric 0÷5Vdc transducer.
PB1 Configuration
0
If configured as digital input
o1
PB2 Configuration
0
If configured as digital input
o1
PB3 Configuration
0
If configured as digital input
o1
PB4 Configuration
0
If configured as digital input
o1
PB5 Configuration
0
If configured as digital input
o1
PB6 Configuration
0
If configured as digital input
o1
PB7 Configuration
0
If configured as digital input
o1
17
3
1
1
999
999
999
max
2
1
1
4
3
3
3
25
c63
25
c63
30
c63
30
c63
30
c63
30
c63
25
c63
M. u.
Resolution