Download dixell IC200CX Series Technical data
Transcript
Ichill 200CX EVO rev 1.1 14/11/2013 When the temperature is inside the neutral zone, a timer is activated (parameter CO53); when this time is elapsed, the Ichill switch on all the compressor to avoid an stationary situation. If the parameter value is 0 the function is non activated. Par. CO54 Maximum time of work in neutral zone without rotation resource When the temperature is inside the neutral zone and only one compressor is ON, a timer is activated (parameter CO54); when this time is elapsed, the Ichill switch off the compressor and swith on an available compresso. If the parameter value is 0 the function is non activated. 18. COMPRESSORS MANAGEMENT 18.1 Compressors Start- Up The parameter CO10 defines the compressor start-up: CO10=0 direct CO10=1 part winding Direct Start-Up It is necessary to configure one relay to drive the contactor of the compressor. EXAMPLE Direct start up configuration for one compressor Fig. 1 Part Winding Start-Up Each compressor needs two relay outputs: Part Winding coil 1 of the compressor; Part Winding coil 2 of the compressor. The time delay between coil 1 and coil 2 activation is CO11 (decimal of second, in a range 0..5 seconds). EXAMPLE Part Winding configuration of the compressor relay outputs RL1: set Par CF41 = c39 Part Winding coil 1 the compressor 1; RL2: set Par CF42 = c40 Part Winding coil 2 of the compressor 1. Compressor Start- up With Part Winding First step: the Part winding coil 1 of the compressor 1 (relay K1 of fig2) is switched on Second step: after the CO11 delay is turned on the Part winding coil 2 of the compressor 1 (relay K2 of fig2). To turn off the compressor the two relay outputs are both turned off at the same time. Pag. 41 of 151