Download USER MANUAL - Sky Elevator
Transcript
CHAPTER 5: UCM SERVICE M6-UCM SERVICE menu is used for EN 81-1/2+ A3 norm related functions. 5-A) U1-CLEAR ERROR This menu is used to clear UCM Errors (Error 64 and Error 72) that caused the system to be blocked. Before clearing the error and removing the blockage, the reason of error must be detected and removed. Error clearing must be performed by only competent person. 5-B) U2-UCM TEST ( SLB4 board is required for ACT/ACS Series) This utility starts Manual UCM Test procedure for Gearless systems and Valve Test procedure for Hydraulic systems. 5-C) U3-TEST TIME This parameter defines the start date and time for periodic Automatic Test Procedure according to EN 81-1/2+A3 norm. It is active only when parameter B59=2 (Daily Check) and RTC is installed. After completing autotest, the test date is automatically assigned to the next day. 5-D) U4-TEST START This parameter defines the number of start period of Automatic Test Procedure according to EN811/2+A3 norm. When the number of start value reaches the multiples of this period, Automatic test is started. It is active only when parameter B59=1 (Start Count) and can be set between 2 and 1500. 5-E) U5 -TEST COUNTER Actual number of starts passing after the last Autotest is counted in this parameter for monitoring purposes. F/7.5.5.02.67 R:10 62 / 62 AC