Download E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers
Transcript
Section 4-4 Executing Heating/Cooling Control Dead Band • For heating/cooling control, the dead band is set with the set point as its center. The dead band width is the set value of the Dead Band parameter (adjustment level). Setting a negative value produces an overlapping band. • If an overlapping band is set, the bumpless function may not operate when switching between manual operation and automatic operation. • The default is 0.0 EU for Controllers with Thermocouple/Resistance Thermometer Universal Inputs and 0.00% FS for Controllers with Analog Inputs. Dead band: Dead band width = A positive value Output Heating side Heating side Cooling side PV 0 Set point Cooling Coefficient Overlapping dead band: Dead band width = A negative value Output Cooling side PV 0 Set point If the heating characteristics and cooling characteristics of the control object are very different and good control characteristics cannot be achieved with the same PID constants, the cooling coefficient can be used to adjust the proportional band (P) for the control output assigned to the cooling side. Use this to achieve balanced control between the heating side and cooling side. The proportional bands (P) for the control outputs assigned to the heating/cooling sides can be calculated using the following equations. P for control output assigned to heating side = P P for control output assigned to cooling side = P for control output assigned to heating side × cooling coefficient The cooling coefficient is multiplied by the P for the control output assigned to the heating side to obtain control with characteristics that differ from those of the control output assigned to the heating side. Output Output P for control output assigned to heatP for control output ing side × 1.0 assigned to heating side × 1.0 P for control output P for control output P for control output P for control output assigned to heating side assigned to heating side assigned to cooling side assigned to cooling side PV PV 0 0 Set point Set point P for control output assigned to P for control output assigned to heating side × 1.5 heating side × 0.8 Automatic Cooling Coefficient Adjustment By executing AT during heating/cooling control, the cooling coefficient can be automatically calculated along with the PID parameters. Parameter name Automatic Cooling Coefficient Adjustment Note Setting rage OFF: Disabled, ON: Enabled Default OFF If there is strong non-linear gain for the cooling characteristics, such as when cooling water boils for cooling control, it may not be possible to obtain the optimum cooling coefficient at the Controller, and control may take the form of 97