application, alarm signaling is arranged by grouping exceeded thresholds from
different channels to a single or several relays.
Control setting to either of the listed output relays activates the selected relay if any
alarm and control threshold is exceeded. Select appropriate threshold and hysteresis
values to support simple binary on/ off control operations. For example, when a
ventilator is connected to a correctly preset output relay and when the High threshold
is set to 50 ˚C with 8 ˚C hysteresis, the fan will be switched on and off when the
temperature level is above 50 ˚C or below 42 ˚C, respectively.
The same as for failure signaling, exceeded threshold notification (along with its date
and time) can be recorded in the Event Log. Depending on the settings, the Event
Log can include Both, Crossing or Releasing entry type.
The recording of measurement results can be controlled by means of exceeded
alarm/control thresholds. Two different recording intervals can be set. The exceeded
threshold can switched from Rec interval I to Rec interval II. In particular, if either
recording interval is set to PAUSE, the recording can be switched on / off when the
threshold (or several thresholds from different channels) is exceeded.
In addition, each alarm/control threshold can have a color (green - low priority,
yellow, red – high priority) assigned. If the threshold is exceeded, the result is
displayed in a different color. If the threshold is exceeded more than once, the
highest priority color is displayed.
8.9.
Totalizers
One or two totalizers can be used for each measurement output and calculated value
with a flow unit. The flow unit needs to be entered as: „…/s”, „…/min”, „…/h”, „Hz” or „kHz”.
The totalizer unit is created automatically be deleting the ending, i.e. if the totaled quantity
is expressed in „kg/h”, the totalizer unit will be „kg”; if the total quantity is expressed in
„Hz”or „kHz”, the totalizer has no unit assigned.
Each enabled totalizer is updated every 1 second according to the instantaneous value
of the totaled quantity. The conversion factor is selected automatically based on the
applicable unit. Example: if the totaled instantaneous value is 180 kg/h, 0.05 kg is added
every second to the totalizer. The value added to the totalizer can be both, positive and
negative.
Totalizer update for binary inputs operating in the frequency measurement mode is
somewhat different. The totalizer value is increased / decreased every 1 second as well,
but according to the number of pulses recorded within the last second. Example: water
mass flow is measured with a pulse water meter. The water meter is connected to a binary
input set to the pulse counting mode. The pulse weight is 10 dm 3. At a specific speed of
the water meter, subsequent pulses arrive every 20 seconds, and the frequency equals
0.05 Hz. Instantaneous value of the mass flow is 0.5 dm3/s. The instantaneous value is not
totaled by the totalizers (if assigned to the input), but instead the totalizers increase their
status by 10 dm3 every 20 seconds, with each incoming pulse.
→ MAIN MENU → SETTINGS → TOTALISERS
TOTALISERS
[1]
01.[Tag]
Totalizer Σ1
[2]
Mode → Totalize (Off, Totalize, Modbus RTU, HART)
[3]
Format → 0000.0 (0.0000, 00.000, .., 00000)