Download IM 613-1: Unit Vent MicroTech Controller - 348KB

Transcript
Table 12.
Connection
Inputs and Outputs for Program UV2***
Units (Models AR)
Software
Model
Component Description
Table 13.
Certified
Connection
Inputs and Outputs for Program UV3***
Units
(Models AZ or AV/AH)
Drawing
Software
Model
Component Description
IN0
All
Tenant override or remote spt. adjust or
both (optional)
IN0
All
Tenant override or remote spt. adjust or
both (optional)
IN1
All
Room temperature sensor
IN1
All
Room temperature sensor
IN2
All
Discharge air temperature sensor
IN2
All
Discharge air temperature sensor
IN3
All
Outdoor air temperature sensor
IN3
All
Outdoor air temperature sensor
IN5
All
Water-in temperature sensor
IN5
All
Not Used
IN6
All
Water-out temperature sensor
& low refrigerant temperature switch
IN6
All
Not Used
IN7
All
Outside air damper position
Outside air damper position
DI-2
All
Day-night changeover device (optional)
DI-3
All
Ventilation lockout (default) or exhaust fan
interlock (optional)
IN7
DI-1
All
All
DI-2
All
DI-3
MDL02
MDL03
Ventilation lockout (default) or exhaust fan
interlock (optional)
Day-night changeover device (optional)
MDL04
Emergency heat switch (SW5)
DI-4
MDL05
High pressure switch (HP)
➀
Not used
Not Used
MDL06
Not used
DI-4
All
High pressure switch (HP)
MDL04
Low DX coil temperature switch (T4)
DI-5
All
Low DX coil temperature switch (T4)
RO-1
All
Fan relay (R4)
RO-2
All
Compressor relay (R1)
RO-3
All
Reversing valve
RO-4
All
Outside air damper open
RO-5
All
Outside air damper close
RO-6
RO-7
RO-8
RO-10
DI-5
RO-1
MDL05
Low DX coil temperature switch (T4)
MDL06
Not used
All
MDL04
RO-2
Fan relay (R4)
Compressor relay (R1 on AZ, R7 on AV/AH)
MDL05
Compressor relay (R7)
MDL06
Not used
MDL02
Electric heat stage 1
RO-3
All
Not used
MDL03
Not used
RO-4
All
Outside air damper open
MDL02
Electric heat stage 2
RO-5
All
MDL03
Not used
MDL02
Electric heat stage 3
MDL03
Not used
All
MDL04
RO-6
Exhaust fan relay or auxilliary heat relay
RO-7
RO-8
RO-10
Outside air damper close
Electric heat stage 1
MDL05
Not used
MDL06
Electric heat stage 1
MDL04
Electric heat stage 2
MDL05
Not used
MDL06
Electric heat stage 2
MDL04
Electric heat stage 3
MDL05
Not used
MDL06
Electric heat stage 3
All
Exhaust fan relay or auxilliary heat relay
Notes:
1.
High pressure switch HP is not installed on AV/AH units.
These units are wired to provide a constant, no-fault
condition.
IM 613 / Page 23 (Rev. 7/99)