1. Place and install the pump on a level, stable
surface in a dry and frost-proof room.
2. Make sure that sufficient air can reach the
cooling fan of the motor. For this purpose the
free space above the cooling fan should be
at least 1/4 of the diameter of the fan cover
air intake.
3. Install the pump with counter flanges. Pumps
with non-standardised connections; counter
flanges are delivered separately.
4. Install a valve on the supply and on the delivery
connection of the pump.
5. If there is a chance that when the pump is
standing still the medium can flow back, it is
advised to install a non-return valve.
6. Make sure that the inlet of the pump is
never clogged.
7.2 MOUNTING A MOTOR ON THE PUMP
ATTENTION
It is advised to use a specially designed
Armstrong motor. Before installing an
other brand/standard IEC-norm motor,
Armstrong-Pumps has to be consulted to verify
the applicability.
The motor has to conform to the following conditions:
 Increased power output (to limit the standard
installed motor power)
 Reinforced bearing at driven end (to withstand the axial force)
 Fixed bearing at driven end (to minimize the
axial play)
 Smooth shaft, no key lock (to improve the
coupling grip and to improve the motor
balance)
7.1.1 INDICATORS
The advised bearings per motor type are:
B
[kW]
Axial bearing
[kW]
Co-axial
bearing
0.37
6203-2RS-C3
11
7309-BEP
0.55
6203-2RS-C3
15
7309-BEP
0.75
6204-2RS-C3
18.5
7309-BEP
1.1
6204-2RS-C3
22
7311-BEP
1.5
6305-2Z-C3
30
7312-BEP
2.2
6305-2Z-C3
37
7312-BEP
3
6306-2Z-C3
4
6306-2Z-C3
5.5
6308-2Z-C3
7.5
6308-2Z-C3
A
The arrow (A) on the pump foot indicates the flow
direction of the liquid. The arrow (B) on the top
bracket indicates the rotating direction of the motor.
7.1.2 INSTALL BYPASS
Install a bypass if the pump operates against a closed
valve. The required capacity of the bypass is at least
10% of the optimum volume flow. At high operating
temperatures a higher volume flow is required. Refer to
the table "Minimum volume flows" in the paragraph
"Working range".
Page 13 of 36