Download - Armstrong Fluid Technology
Transcript
1. Place and install the pump on a level, stable surface in a dry and frost-proof room. 2. Make sure that sufficient air can reach the cooling fan of the motor. For this purpose the free space above the cooling fan should be at least 1/4 of the diameter of the fan cover air intake. 3. Install the pump with counter flanges. Pumps with non-standardised connections; counter flanges are delivered separately. 4. Install a valve on the supply and on the delivery connection of the pump. 5. If there is a chance that when the pump is standing still the medium can flow back, it is advised to install a non-return valve. 6. Make sure that the inlet of the pump is never clogged. 7.2 MOUNTING A MOTOR ON THE PUMP ATTENTION It is advised to use a specially designed Armstrong motor. Before installing an other brand/standard IEC-norm motor, Armstrong-Pumps has to be consulted to verify the applicability. The motor has to conform to the following conditions: Increased power output (to limit the standard installed motor power) Reinforced bearing at driven end (to withstand the axial force) Fixed bearing at driven end (to minimize the axial play) Smooth shaft, no key lock (to improve the coupling grip and to improve the motor balance) 7.1.1 INDICATORS The advised bearings per motor type are: B [kW] Axial bearing [kW] Co-axial bearing 0.37 6203-2RS-C3 11 7309-BEP 0.55 6203-2RS-C3 15 7309-BEP 0.75 6204-2RS-C3 18.5 7309-BEP 1.1 6204-2RS-C3 22 7311-BEP 1.5 6305-2Z-C3 30 7312-BEP 2.2 6305-2Z-C3 37 7312-BEP 3 6306-2Z-C3 4 6306-2Z-C3 5.5 6308-2Z-C3 7.5 6308-2Z-C3 A The arrow (A) on the pump foot indicates the flow direction of the liquid. The arrow (B) on the top bracket indicates the rotating direction of the motor. 7.1.2 INSTALL BYPASS Install a bypass if the pump operates against a closed valve. The required capacity of the bypass is at least 10% of the optimum volume flow. At high operating temperatures a higher volume flow is required. Refer to the table "Minimum volume flows" in the paragraph "Working range". Page 13 of 36