Setting Up the PowerStation for Use in a Hazardous Environment
PowerStations ordered with the Class 1, Division 2 Hazardous Location option ship with a bracket for use with
AC units. You must have this bracket installed in order to be compliant with Class 1, Division 2 guidelines in a
hazardous environment. This prevents the power switch from accidently being turned off or the power cord
being accidentally pulled out from the unit. The other end of the power cord has a stripped and prepared end for
attachment to a terminal strip according to Hazardous Location requirements.
Follow the instructions below after the PowerStation has been mounted:
1)
Plug the power cord into the connector.
2)
Place the bracket over the power cord and attach the bracket with the screw provided to
secure it to the PowerStation as shown in the following figure.
3) Attach the leaded end of the power cord to a (20A) main branch circuit with a tightening
torque of 7.0lbs/in (0.79 N-m).
IPC/IPX PowerStation Series Hardware User Guide