Ripple
Transient
Protection
Response Time
9.8
Less than 10µs for 10% to 90% signal change
Turbine Meter Counter Input
Type
Turbine Meter
Sensitivity
Transient
Protection
Isolation
9.9
Transient: 2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
Counter 1
Single turbine meter input.
Designed for use with low voltage, turbine meter outputs.
Minimum input 30mVp-p at 5-50Hz.
Minimum input 150mVp-p at 150Hz.
Minimum input 650mVp-p at 5kHz.
Minimum input 750mVp-p at 10kHz.
Maximum input 4Vp-p using internal amplifier.
2.5kV surge withstand capability as per ANSI/IEEE C37.90.11989
Common ground return connected to Chassis Ground.
Digital Counter Input
Type
Frequency
Input Thresholds
Contact Resistance
Transient
Protection
Isolation
9.10
Counter 0.
Dry contact input.
Wetting current typically 5mA.
Contact closure to ground is ON.
Open input is OFF.
0-10kHz.
0.8V typical turn on input voltage.
Less than 0.4V guaranteed turn on input voltage.
1.5V typical turn off input voltage.
Greater than 2.0V guaranteed turn off input voltage.
ON input requires less than 100Ω contact resistance.
OFF input requires greater than 1kΩ contact resistance.
2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
Common ground return connected to Chassis Ground.
Digital Output
Type
Load Range
Transient
Protection
Isolation
Note
Open drain sinking
500mA maximum
30VDC maximum
2.5kV surge withstand capability as per ANSI/IEEE C37.90.11989
Common ground return connected to Chassis Ground.
Digital Output available on version 5 and later controller
hardware.