Download STADT PENTA USER MANUAL
Transcript
SINUS PENTA INSTALLATION INSTRUCTIONS Figure 53: Signal sent from a Push-pull, +24V output 3.5.3.5. TECHNICAL SHEET FOR DIGITAL INPUTS Specification MDI input voltage related to CMD Voltage for logic level 1 between MDI and CMD Voltage for logic level 0 between MDI and CMD Current absorbed by MDI at logic level 1 Input frequency for “fast” inputs MDI6, MDI7, MDI8 Duty-cycle allowed for frequency input Min. time period at high level for “fast” inputs MDI6, MDI7, MDI8 Voltage of isolation test between CMD (22) with respect to CMA (1,9) 112/373 Min. Type Max. Unit of m. -30 30 V 15 24 30 V -30 0 5 V 5 9 12 mA 155 kHz 30 50 70 % 4.5 μs 500Vac, 50Hz, 1min. CAUTION Avoid exceeding min. and max. input voltage values not to cause irreparable damages to the equipment. NOTE Isolated supply output is protected by a self-resetting fuse capable of preventing the inverter internal power supply unit from damaging due to a short-circuit. Nevertheless, if a short-circuit occurs, the inverter could lock and stop the motor.