10 PID SETTING
Zone hysteresis
The hysteresis can be set with respect to the zone set value.
This hysteresis is valid for all zone set values.
3-21
Zone PID1:
HYS1:
(3)
OFF
2.0
Setting range
Initial value
0 to 10000 Unit
20 Unit
PID zone
Set the zone (temperature range) to be used by the zone PID function for each PID No.
3-1
PID01-OUT1
P:
3.0%
MR: 0.0%
I:
120s
SF: 0.40
D:
30s ZN:
0.0℃
Note
Setting range
Initial value
Within measuring range
0 Unit
Š When the same zone value is set to two or more PID Nos., the PID having the
smallest No. is executed.
Š To use the Zone PID function, Zone hysteresis and Zone PID must be set.