3-3-2 For NSH-series PTs
Using 9-pin RS-232C Communication expansion board (FX[][]-232-BD) or 9 pin
RS-232C Communication special adapter (FX3U-232-ADP, FX2NC-232ADP)
Use the NSH 5-232UL-[]M cable for NSH-series, and connect its D-Sub connector to
the computer link unit using the cable below.
NSH special cable
(NSH5-232UL-[]M)
Connector
D-Sub
9 pin
Female
FX series Communication expansion board
or Communication special unit
Signal
Pin No.
Pin No.
Signal
FG
1
1
CD
RD
2
2
RD
SD
3
3
SD
CS
4
4
ER
RS
5
5
SG
6
6
DR
7
7
+5V
Screw
m m , Fem ale
SG
8
8
9
9
Hood
Shield
Connector
D-Sub
9 pin
Female
Hood
Using 25-pin RS-232C Communication special adapter (FX0N-232-ADP)
Use the NSH 5-232UL-[]M cable for NSH-series, and connect its D-Sub connector to
the computer link unit using the cable below.
NSH special cable
(NSH5-232UL-[]M)
Connector
D-Sub
9 pin
Female
FX series Communication special adapter
( 25 pin type)
Signal
Pin No.
Pin No.
Signal
FG
1
1
FG
RD
2
2
SD
SD
3
3
RD
CS
4
4
RS
RS
5
5
CS
6
6
DR
7
7
SG
+5V
Screw
m m , Fem ale
8
SG
9
Hood
Shield
35
20
ER
Hood
Connector
D-Sub
25 pin
Male