Shenzhen Gozuk Co., Limited www.gozuk.com Upper limit freq Center freq Lower limit freq Swing freq upper/lower limit Fig.6-25 swing freq. upper/lower limit 20: Set running time arrival. When VFD total running time (P3.40) reaches set running time (P3.39), it outputs index signal. 21: upper pressure alarm signal. On closed-loop control, VFD output alarm signal when the pipeline pressure is greater than the upper limit of pressure. 22: Lower pressure alarm signal. On closed-loop control, VFD output alarm signal when the pipeline pressure is lower than the lower limit of pressure. Freq arrival detection range Range: 5.00Hz (FAR) 0.00~50.00Hz This function is a complement to function 1 listed in Table 6-6. When VFD output frequency is in the "+ -" detection range of set frequency, it outputs pulse signal shown as Fig.6-25. P4.14 - 93 -