Download "user manual"
Transcript
Application Manual In Fig. 6.15 four curves from the simulation is shown which are equal to the results in [2]. 300 3000 [k V ] [A ] 200 2000 100 1000 0 0 -100 -1000 -200 0 5 10 (file E xa_6.pl4; x-var t) v:P OS 1 15 c :V S A -V A v:P OS 2 20 25 30 [m s] -2000 35 c:P OS 2 -XX0078 Fig. 6.15 - ATP simulation results. 6.5 Switching studies using JMarti LCC objects The LCC modeling features of ATPDraw are described in detail in section 5.3 of the Advanced Manual. Line modeling by LCC objects means that user specifies the geometrical arrangement and material constants, then ATPDraw executes ATP's Line/Cable Constants routine and converts the output punch-file to DBM library format. The resulting LIB-file will then be included in the final ATP-file via a $Include call. The JMarti option is one out of the five alternatives supported by ATPDraw's LCC object. Here two switching transient simulation examples are presented. 6.5.1 JMarti model of a 500 kV line (Exa_7.adp) The 3-phase switching example (Exa_3.adp) created in section 6.1 of this manual is repeated here. This time the 500 kV overhead line is represented by a frequency dependent 3-phase JMarti model. The example circuit is shown in Fig. 6.16. Fig. 6.16 - JMarti line in switching study (Exa_7.adp) The overhead in this example is a 138 miles long single circuit 500 kV line (from John Day to Lower Monumental in Oregon, USA) with two sky wires taken from ATP benchmark DCN3.DAT. The line configuration is given in Fig. 6.17. 190 ATPDraw for Windows version 3.5