Download Foreword
Transcript
Chapter 6 EM9 series variable… EM9 User’s manual 5: PID Inverters operate in PID control mode, and need to set F9 group (PID control), when select this frequency command source. The reference frequency is the result of PID adjustment. For detailed PID preset source, preset and feedback source, please refer to description of F9 group (PID function). 6: Communication The reference frequency is set by host through communication. For details, please refer to communication protocol. 7: Program timing operation (Simple PLC) User can set reference frequency, hold time, running direction of each step and acceleration/deceleration time between steps. For details, please refer to description of F8.19. 8: PUL (only for X1 Terminal) The frequency command is set by input pulse from X1 terminal, setting range refer to parameter(F5.19~F5.23). 9: Program run length refer to parameter(F8.31~F8.32). Code Name Description Setting Range Factory setting 0: Keypad digital 1: Keypad potentiometer 2: AI1 0~5 1 F0.03 Auxiliary frequency channel 3: AI2 4: Communication 5: PUL 0: Keypad digital Through change the value of function code F0.05 (Keypad reference frequency) to set frequency by keypad. 1: Keypad potentiometer。 Set frequency by keypad potentiometer。 2: AI1 3: VAI2 4: Communication The reference frequency is set by host through communication. For details, please refer to communication protocol. 5: PUL(only for X1 terminal) Code Name Description Setting Range Factory setting 0: Main Channel Valid 1: Auxiliary Channel Valid 2: Main + Auxiliary Main-auxiliary Channel 0~6 0 F0.04 3: |Main – Auxiliary| Combination 4: MAX(Main Auxiliary) 5: MIN(Main Auxiliary) 6: Terminal Switch Select the frequency command input channels of inverters. There are 7 kinds frequency commands input channels for selection. 0: Main Channel Valid 1: Auxiliary Channel Valid 2: Main + Auxiliary 3: Main - Auxiliary 4: MAX(Main Auxiliary) 5: MIN(Main Auxiliary) 6: Terminal Switch: Select from the multi-function input terminal as the primary channel or secondary channel frequency for a given end. Code Description Setting Range Factory setting 0.00 Hz~F0.06 0.00~F0.06 F0.05 keypad reference frequency 50.00H (Maximum frequency) When frequency command is set to “keypad digital”, this function code value is the initial value of inverter reference frequency. 19 Name