Download EJX910A and EJX930A Fieldbus Communication Type
Transcript
APPENDIX 3. INPUT SELECTOR (IS) BLOCK When SELECT TYPE is “Minimum” The IS block selects the input with the minimum value among valid inputs and transmits the value of that input to OUT. The number of the selected input is transmitted to SELECTED. SELECTION IN_1 = 23 IN_2 = 34.5 OUT = 2.34 IN_3 = 45 IN_4 = 2.34 IN_5 = 23.6 SELECTED = 4 IN_6 = 15.5 IN_7 = 32.5 IN_8 = 27.4 SELECT_TYPE = Minimum STATUS_OPTS DISABLE_1 = OFF MIN_GOOD = 1 DISABLE_2 = OFF DISABLE_3 = OFF DISABLE_4 = OFF DISABLE_5 = OFF DISABLE_6 = OFF DISABLE_7 = OFF DISABLE_8 = OFF OP_SELECT = 0 FA0305.EPS Figure A3.5 Example (4) A-27 IM 01C25R03-01E