Download Manual IMPACT67-EC

Transcript
Manual
IMPACT67 | EtherCAT
Connection Possibilities
Supply cable .................................................................. : 2 × connector 7/8" female / male connector
Data cable ..................................................................... : 2 × M12 connector 5-pin
....................................................................................... : (male connector, D-coded)
Inputs ............................................................................. : 8 × 5-pin M12 connector
Maximum length of input cable ......................................: < 30 m
Power Supply
Voltage Us over 7/8” power in connector ......................: 24 VDC
Voltage Us range ...........................................................: 18 – 30 VDC
Sensor supply 7/8” power in connector .........................: max. 9 A
Current consumption (without In-/Output) .....................: ≤ 130 mA
Inputs
Number of inputs ...........................................................: 16
Input characteristics.......................................................: EN 61131-2 Type 2
Supply for sensors .........................................................: max. 200 mA per socket
Short circuit protection for sensors ...............................: Multifuse,
....................................................................................... up to 100 mA load: automatic startup
....................................................................................... from 100 mA load: a reset is required
Multi-fuse reaction time (time to trip) ............................: 1s at IK ≥ 1 A and 23 °C
Derating Supply for Sensors
I(mA)
250
200
150
100
50
0
0
20
30
40
50
T(°C)
68