Download CD3200 Thyristor Unit
Transcript
CD Automation srl CD3200 from 125A to 700A User’s Manual 7.5 Diagram of control connection Caution: this procedure must be performed only by qualified persons. L1 L1 L2 L2 * 1 L1 * 1 2 2 3 Reset - + - + 8 POT 10K 7 0-10Vdc 6 4-20mA Fan Power Supply 5 Input: 4 9 10 11 8Vdc 12 13 + Digital Input - 24Vdc 15 16 17 18 19 T1 20 NC COM NO + - 14 External Current Limit Profiling 0-10Vdc H.B. Contact TO LOAD NOTE: • * The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator. • *² The auxiliary voltage supply of the CD3200 unit must be synchronized with load voltage power supply. If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage (to the load), use an external transformer as designated. • To work, the Reset Contact on terminal 7 and 8 must be closed. Load Type L2 T1 Resistances and Infrared Lamps L2 T1 Variable Resistances Super kanthal or Silicon carbide elements 21 L2 T1 Transformers and Inductances