Download ACS800 Programming Manual

Transcript
177
Index
96.07
96.08
96.09
96.10
96.11
96.12
Name/Selection
Description
FbEq
CONTROL DEV
See parameter 15.01.
12
ACTUAL 1
See parameter 15.01.
13
ACTUAL 2
See parameter 15.01.
14
COM.REF5
See parameter 15.06.
15
PARAM 96.12
Source selected by parameter 96.12.
16
INVERT EXT AO2
Activates the inversion of analogue output AO2 of the analogue I/O extension
module. The analogue signal is at its minimum level when the drive signal
indicated is at its maximum and vice versa.
NO
Inactive
0
YES
Active
65535
MINIMUM EXT AO2
Defines the minimum value for analogue output AO2 of the analogue I/O
extension module. See parameter 96.03.
0 mA
0 mA
1
4 mA
4 mA
2
10 mA
10 mA
3
12 mA
12 mA
4
FILTER EXT AO2
Defines the filtering time constant for analogue output AO2 of the analogue I/O
extension module. See parameter 15.04.
0.00 … 10.00 s
Filtering time constant
SCALE EXT AO2
Defines the scaling factor for analogue output AO2 of the analogue I/O
extension module. See parameter 15.05.
10 … 1000%
Scaling factor
100 …
10000
EXT AO1 PTR
Defines the source or constant for value PAR 96.11 of parameter 96.01.
1000 =
1 mA
-255.255.31 …
+255.255.31 / C.32768 … C.32767
Parameter index or a constant value. See parameter 10.04 for information on
the difference.
-
EXT AO2 PTR
Defines the source or constant for value PAR 96.12 of parameter 96.06.
1000 =
1 mA
-255.255.31 …
+255.255.31 / C.32768 … C.32767
Parameter index or a constant value. See parameter 10.04 for information on
the difference.
-
98 OPTION MODULES
0 … 1000
Activation of the option modules.
The parameter settings will remain the same even though the application
macro is changed (parameter 99.02).
98.01
ENCODER MODULE
Activates the communication to the optional pulse encoder module. See also
parameter group 50 ENCODER MODULE.
NTAC
Communication active. Module type: NTAC module. Connection interface:
Fibre optic DDCS link.
0
Note: Module node number must be set to 16. For directions, see the
NTAC-0x/NDIO-0x/NAIO-0x Module Installation and Start-up Guide
[3AFY58919730 (English)].
NO
Inactive
1
RTAC-SLOT1
Communication active. Module type: RTAC. Connection interface: Option
slot 1 of the drive.
2
Actual signals and parameters