Diagnosis
7.4
Diagnosis Messages of Called Blocks
Error messages of SFC 6 and SFC 20 at the output STATUS_MODBUS
STATUS Event text
Remedy
(Hex)
7xxx
For detailed information please refer to the online help
of SIMATIC Manager.
See online help (SIMATIC
manager -> mark block -> key F1)
8xxx
For detailed information please refer to the online help
of SIMATIC Manager.
See online help (SIMATIC
manager -> mark block -> key F1)
Error messages of FB 63, FB 64, FB 65 and FB 66 at the output STATUS_CONN
STATUS Event text
Remedy
(Hex)
7xxx
For detailed information please refer to the online help
of SIMATIC Manager.
See online help (SIMATIC
manager -> mark block -> key F1)
8xxx
For detailed information please refer to the online help
of SIMATIC Manager.
See online help (SIMATIC
manager -> mark block -> key F1)
7.5
Diagnosis Messages of SFC24
Error messages of SFC24 at the output STATUS_MODBUS
STATUS Event text
Remedy
(Hex)
80A1
DB Number = 0 or too large for the PLC
Choose a valid DB number.
This error code is also reported, when FB
MODBUSPN is called with different instance DBs in
OB1 or cyclic interrupt OB and OB100.
Use the same IDB for the call of
MODBUSPN in OB1 or cyclic
interrupt OB and OB100.
80B1
The DB does not exist in the PLC.
All data blocks that are specified
in DB_x must be created and
copied into the PLC.
80B2
DB UNLINKED
DB must not be created as
UNLINKED.
MODBUS / TCP communication via the integrated PN interface of the CPU
2XV9450-1MB02; Manual edition 2.1
7-12