3.1 Precautions on Wiring
„ Noise Prevention
Example of Wiring for Noise Prevention
SERVOPACK
SJDE
U
V
W
L2
Noise filter
L1
200 VAC
2LF
Min. wire size
: 3.5 mm2
Casing
* 1.
CN2
Servomotor
M
(FG)
PG
CN1
• Operation relay sequence
• User signal generating circuit
Min. wire size
: 3.5 mm2
P
* 2.
P
Casing
1LF
AVR
P (Grounding)
Casing
Min. wire size
: 3.5 mm2
2 mm2 or larger
2
Casing Min. wire size: 3.5 mm *1.
Min. wire size: 3.5 mm2 *1.
Casing
Grounding plate
Groudning: Ground to one point only.
Min. grounding resistance: 100 Ω
* 1. For the wires connected to the casings for installation purposes, use wires with a diameter of 3.5 mm2
or larger. Flat braided copper wires are recommended.
* 2. Use twisted pair wires for section P.
Correct Grounding
• Servomotor frame grounding:
Be sure to connect the FG grounding terminal on the frame of the servomotor to the grounding terminal on the SERVOPACK.
• Be sure to ground the grounding terminal of the SERVOPACK.
• If the wires of the servomotor’s main circuit are laid in a metal conduit, ground the conduit and the
grounding box.
One-point grounding must be used.
20