Download Junma Users Manual
Transcript
TOEP_C710806_01A_0_0.book Seite 20 Montag, 2. Juli 2007 4:24 16 3.1 Precautions on Wiring Noise Prevention Example of Wiring for Noise Prevention SERVOPACK SJDE U V W L2 Noise filter L1 200 VAC 2LF Min. wire size : 3.5 mm2 Casing * 1. CN2 Servomotor M (FG) PG CN1 • Operation relay sequence • User signal generating circuit Min. wire size : 3.5 mm2 P * 2. P Casing 1LF AVR P (Grounding) Casing Min. wire size : 3.5 mm2 2 mm2 or larger 2 Casing Min. wire size: 3.5 mm *1. Min. wire size: 3.5 mm2 *1. Casing Grounding plate Groudning: Ground to one point only. Min. grounding resistance: 100 Ω * 1. For the wires connected to the casings for installation purposes, use wires with a diameter of 3.5 mm2 or larger. Flat braided copper wires are recommended. * 2. Use twisted pair wires for section P. Correct Grounding • Servomotor frame grounding: Be sure to connect the FG grounding terminal on the frame of the servomotor to the grounding terminal on the SERVOPACK. • Be sure to ground the grounding terminal of the SERVOPACK. • If the wires of the servomotor’s main circuit are laid in a metal conduit, ground the conduit and the grounding box. One-point grounding must be used. 20