Modicon M580 Racks In a local rack, as many as 7 extender racks of X80 may be added (see page 59). Switch Rack Address 0 1 2 3 4 5 6 7 1 OFF OFF OFF OFF 2 OFF OFF ON ON ON ON ON ON OFF OFF ON ON 3 OFF ON OFF ON OFF 4 Not used ON OFF ON By default, the rack extender module is shipped with the switches set to address 0 (all switches OFF). Address 0 is reserved for only the main local rack (which contains the CPU). The remaining X80 racks in an extension may be assigned addresses 1 through 7 in any order or sequence. The key requirement when you set the X80 rack addresses is that each address is unique with respect to all other rack addresses in the extension. NOTE: You create a condition called a collision if you: assign the same rack address to more than one X80 rack in an extension assign address 0 to any rack other than the main local rack When a collision happens, one of the racks with the duplicate rack address will not operate. To recover from a collision: Step Action 1 Turn OFF the power supplies in the racks that have the address mismatch. 2 Using the address switches on the rack extender module, set unique and correct rack addresses. 3 Reapply power to the racks. Rack Extender LEDs The LEDs on the rack extender module provide status information about the rack in which it resides: EIO0000001578 10/2013 63