Download Modicon M580 - Hardware - Reference Manual
Transcript
M580 CPU Configuration Configuring the Size and Location of Inputs and Outputs Introduction Use the following steps to configure the size and starting positions of inputs and outputs. Your own project configuration may differ. Setting Global Addresses and Operating Mode Parameters Edit the communication module inputs and outputs: Step Action 1 Double-click the left mouse button on the image of the M580 CPU in the PLC Bus to view its properties. 2 Select the Configuration tab. 3 You can check the Operating mode boxes to enable these parameters in your application: Run/Stop input (default: Not Selected) Memory protect (default: Not Selected) Automatic start in Run (default: Not Selected) Initialize %MWi on cold start (default: Selected) Cold Start Only (default: Not Selected) 4 Select the size of the global addresses: %M (maximum value: 32,634) %MW (maximum value: 65,232) %KW (maximum value: 32,760) %S (maximum value: 128) %SW (maximum value: 168) 5 Select the Online modification in RUN or STOP check box (in the Configuration Online Modification field) to use the change configuration on the fly (CCOTF) feature. 6 Select Edit →Validate (or click the toolbar button) to save the configuration. NOTE: After you validate module settings for the first time, you cannot edit the module name. If you subsequently decide to change the module name, delete the existing module from the configuration, then add and rename a replacement module. Completing the Ethernet Network Configuration After you configure these settings, configure the CPU settings beginning with its Channel Properties (see page 188). Then configure the Ethernet network devices. EIO0000001578 10/2013 149