Download PCE830/40 User Manual
Transcript
PCE840 Danaher Motion Parameter Data IDN IDN 32838: Motor 2 Name Binary Data The Motor variable is a 32-bit long unsigned long integer which is used to identify the waveshape downloaded to the PCE840 controller. By convention the 4 ASCII character abbreviation of the motor name is converted to an integer and downloaded along with the waveshape. Used to assign a label to Wave Shape Generation Table created. Conversion Scaling Factor: Data Length: Minimum Value: Maximum Value: Access State: 1 4 bytes 0 0xFFFFFFFF Read/Write in Phase 2 Read-only in Phase 3 and 4 Parameter Data IDN IDN 32840: Kvff Unsigned Decimal Number Allows following error to be reduced when running at a constant speed. When the drive is commanded to run at a constant speed, kvff = 1000 will reduce the steady state following error to zero, but will cause overshoot. A value of 700 is typically used. Conversion Scaling Factor: Data Length: Units: Minimum Value: Maximum Value: Access State: 0.1 2 bytes Percent 0 1,999 Read/Write by the Master Parameter Data IDN IDN 32840: ARZ0 Unsigned Decimal Number ARZ0 is the first velocity loop compensation zero. Please refer to Section 3.7, Servo Loop Parameters for additional information. Conversion Scaling Factor: Data Length: Units: Minimum Value: Maximum Value: Access State: 3-110 1 4 bytes Hz 20 100,000 Read/Write by the Master PCE830/40 User Manual