Download vacon user manual
Transcript
Layout, connections and installation vacon • 19 Using the cable clamp included in the delivery of the drive, ground the shield of the PROFIBUS cable to the frame of the AC drive. NOTE: This can be done in all drives if there is no difference in PE potential between the drives. However, if there is PE potential difference then the shield should be connected to PE only at one point in the system. The shields of the cables shall be joint but not connected to several PE points with different potential. 7 For MR4: 1. Tighten the grounding cable tie around the stripped part of the cables. 2. Place the end of the grounding cable tie under an earthing lamella (supplied with the drive) and fix it tightly with a screw on the PROFIBUS grounding bracket. 3. 3 1 2 Cut off the end of the cable tie. 24-hour support +358 (0)201 212 575 • Email: [email protected] 4