Transcript
vacon • 58 6.3.3.1 PROFIBUS DP interface DP-V1 header The DP-V1 response header consists of 4 fields, each one octet in size. Octet number Field name Description Allowed values Use 0x5E for read requests. 1 Function Number PROFIBUS DP-specific operation number. Use 0x5F for write requests. Other values are not used in the Parameter Access. 2 3 4 6.3.3.2 Slot Number PROFIBUS DP-specific refThis value is mirrored from the associated erence to internal device request. module. Index PROFIBUS DP-specific index used to address different properties. Data Length Number of data octets in the parameter request frame. This count excludes the DP-V1 header. Use 47 for Parameter Access in OPTE5/E3. Other values should not be used for Parameter Access. Number of octets in response header, parameter address(es) and parameter value(s) fields. Error response If an error occurred in the Parameter Access, the response provided by the slave is an error response. Its PROFIBUS DP-V1 header contents differ from a normal read/write response. An error response contains 4 octets as described below. Octet number Field name Description Allowed values The slave returns 0xDE to indicate an error read response. 1 Function Number PROFIBUS DP-specific operation number. The slave returns 0xDF to indicate an error write response. Other values are not used in the Parameter Access. 6 2 Error Decode Defines how the error information in the following two fields should be decoded. Always 128 in PROFIdrive. 3 Error Code 1 High 4 bits indicate error class, 4 lower bits indicate error code. See chapter 6.3.3.3. 4 Error Code 2 Application-specific. Always 0 in PROFIdrive. Other values are not used in the Parameter Access. Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205