Download 1775-6.4.1, PLC-3 Family Programmable Controller, Programming
Transcript
Chapter 14 Addressing Memory and Monitoring Controller Status Figure 14.9 Minor Fault Status Bits (Status File 0, Word 2) 17 16 15 14 13 12 11 10 07 Interrupt overlap Battery high 06 05 04 03 02 01 00 Peer–to–peer or backup communication error Single–bit error Battery low Thermal fault Minor I/O fault Bit Title The processor sets this bit when 10 peer-to-peer or backup communication error the primary or backup processor detects a backup communicaiton error, the master processor detects a peer-to-peer communication error, or the data transmitted exceeds the size of the specified input file 11 single-bit error an error correcting (EDC) memory module detects single-bit errors 12 thermal fault a thermistor on the processor detects incoming ambient air temperature higher than 60°C or 140°F 13 minor I/O fault communication disrupts between a scanner and an I/O adapter 14 battery low a memory module contains a battery that lacks sufficient charge 15 battery high a memory module containing a lithium battery has an overvoltage condition. If you are using a nicad battery, do not monitor this bit. 16 interrupt overlap the real-time interrupt routine exceeds the set point specified through LIST 14-17