Download "user manual"

Transcript
Building Envelope General Information
Figure 5-F—Insulation in Substantial
Contact
Figure 5-G—Blown Insulation Above
Sloping Ceiling
For most United States cities, the
climate zone map in Figure 5-E and the
listing in Table B-1 of Appendix B will be
enough to determine the appropriate
climate zone. Some U. S. counties,
however, have significant elevation
changes within the county that affect
climate. In these instances, if there are
recorded historical climatic data available
for a construction site, Table B-3 of
Appendix B may be used to determine the
climate zone. Such a determination
requires the approval of the authority
having jurisdiction.
Space-Conditioning
Categories (§ 5.1.2)
The envelope requirements apply to three
types of spaces: nonresidential, residential,
and semiheated. Both nonresidential and
residential are conditioned spaces; for
these the Standard calls for more
insulation and more control of heat gain
through fenestration. Most spaces within
buildings that are covered by the Standard
will fall into one of these three categories.
The residential space category includes
spaces in buildings used primarily for
living and sleeping. Examples include, but
are not limited to, dwelling units,
hotel/motel guest rooms, dormitories,
nursing homes, patient rooms in hospitals,
lodging houses, fraternity/sorority houses,
hostels, prisons, and fire stations.
The nonresidential space category
includes all other conditioned spaces
covered by the Standard including, but not
limited to, offices, retail shops, shopping
malls, theaters, restaurants, meeting
rooms, etc. The defining characteristic of
nonresidential spaces is that they are not
continuously conditioned. Offices, for
instance, are typically conditioned only
during the day on weekdays and part of
the day on Saturday; they are generally not
conditioned on Sundays and holidays.
Residential spaces, on the other hand, are
conditioned on a more-or-less continuous
basis. A greater investment in energy
efficiency can be justified for spaces that
are continuously conditioned, and this is
the basis of the distinction between these
two space categories.
As discussed earlier, under certain
circumstances, spaces can be either
semiheated or unconditioned. Examples
of semiheated spaces are warehouses or
light manufacturing facilities that have
only a limited heating system (no cooling).
In order to qualify as a semiheated space,
the heating system must be sufficiently
small, with the exact maximum output
capacity depending on the climate (see
Conditioned Space in the Reference
section). Unconditioned spaces are spaces
that have neither a heating nor a cooling
system. The general assumption is that all
spaces in climates 3 through 8 are
conditioned. Declaring a space as
semiheated or unconditioned is an
exception that must be approved by the
building official, although the Standard
has very specific criteria for making the
determination. The designer should label
semiheated and unconditioned spaces on
the construction plans that are submitted
with the building permit application. This
will enable the building official to verify
that the spaces are truly semiheated or
unconditioned.
Some spaces are considered
conditioned even though they may not
have a heating system or cooling system
that directly serves the space. This type of
space is called indirectly conditioned (see
Conditioned Space in the Reference
section). The nonresidential and residential
building envelope requirements apply to
indirectly conditioned space in the same
way that they apply to directly conditioned
space. Examples of indirectly conditioned
spaces are storage rooms that are adjacent
to conditioned spaces, toilets that exhaust
air from conditioned spaces, or electrical
closets that are adjacent to conditioned
spaces.
Most of the time it will be easy to
identify indirectly conditioned spaces.
When there is uncertainty, the Standard
has two criteria to determine what
constitutes indirectly conditioned space:
1. The heat transfer rate to
conditioned space is larger than the heat
transfer rate to the exterior (ambient
conditions). This will cause the
--`,``,``,`,,,,,`````,`,```,```,-`-`,,`,,`,`,,`---
5-8
Copyright ASHRAE
Provided by IHS under license with ASHRAE
No reproduction or networking permitted without license from IHS
User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007
Licensee=AECOM/5906698001, User=li, xiaoxiao
Not for Resale, 07/02/2009 03:02:18 MDT