Using the Command Interface
Overview of the Command Interface
Table B–2:
Command Codes
Command
Code
Command
Parameter Register
4110
None
Parameters
0 = Present and previous
months
Description
Resets min/max.
1 = Present month
2 = Previous month
5110
None
None
Resets all demand registers.
5111
None
None
Resets current demand.
5113
None
None
Resets power demand.
5114
None
None
Resets input demand.
5115
None
None
Resets generic demand for first group of 10
quantities.
5210
None
None
Resets all min/max demand.
5211
None
None
Resets current min/max demand.
5213
None
None
Resets power min/max demand.
5214
None
None
Resets input min/max demand.
5215
None
None
Resets generic 1 min/max demand.
Start new demand interval.
Bit 0 = Power Demand
5910
8001
Bitmap
1 = Current Demand
2 = Input Metering Demand
3 = Generic Demand Profile
Preset Accumulated Energies
Requires the IO Data Pointer to point to registers
where energy preset values are entered. All
Accumulated energy values must be entered in
the order in which they occur in registers 1700 to
1727.
6209
8019
I/O Data Pointer ➁
6210
None
None
6211
None
None
Clears all accumulated energy values.
6212
None
None
Clears conditional energy values.
Clears all energies.
6213
None
None
Clears incremental energy values.
6214
None
None
Clears input metering accumulation.
➀You must write to register 8001 the number that identifies which output you would like to use. To
determine the identifying number, refer to“I/O Point Numbers” on page 159 for instructions.
➁Data buffer location (register 8019) is the pointer to the first register where data will be stored. By default, return
data begins at register 8020, although you can use any of the registers from 8020–8149. Take care when assigning
pointers. Values may be corrupted if two commands are using the same register.