Input/Output Capabilities
Digital Inputs
INPUT/OUTPUT
CAPABILITIES
Digital
Inputs
The power meter can accept one digital input. A
digital input is used to detect digital signals. For
example, the digital input can be used to determine
circuit breaker status, count pulses, or count motor
starts. The digital input can also be associated with
an external relay. You can log digital input transitions
as events in the power meter’s on-board alarm log.
The event is date and time stamped with resolution to
the second. The power meter counts OFF-to-ON
transitions for each input, and you can reset this value
using the command interface.
The digital input has three operating modes:
•
Normal—Use the normal mode for simple on/off
digital inputs. In normal mode, digital inputs can
be used to count KY pulses for demand and
energy calculation.
•
Demand Interval Synch Pulse—you can
configure any digital input to accept a demand
synch pulse from a utility demand meter (see
“Demand Synch Pulse Input” on page 44 of this
chapter for more about this topic). For each
demand profile, you can designate only one input
as a demand synch input.
•
Conditional Energy Control—you can configure
one digital input to control conditional energy (see
“Energy Readings” on page 38 in Chapter 4—
Metering Capabilities for more about conditional
energy).
NOTE: By default, the digital input is named DIG IN
502 and is set up for normal mode.
For custom setup, use SMS to define the name and
operating mode of the digital input. The name is a 16character label that identifies the digital input. The
operating mode is one of those listed above. See the
SMS online help for instructions on device set up of
the power meter.