Download OPERATION MANUAL Motion Control Unit
Transcript
Section 3-5 Connecting MECHATROLINK Devices 3-5-4 Counter Module, Pulse Output Module Communications setting For counter modules and pulse output modules, MECHATROLINK communications can be set using the DIP switches. 1 SW (Default setting) 2 3 4 5 6 7 8 ON OFF Transmission setting MECHATROLINK communications can be specified using the DIP switches (SW) 6 to 8. See the table below. Any change of the settings becomes valid after turning OFF the power once, then ON again. Pin 6 Name Baud rate Setting OFF 7 ON Transmission bytes OFF 8 ON OFF Station address Content 4Mbps Default setting OFF 10Mbps 17byte OFF 30byte Refer to Station address setting ON ON (Do not set to OFF.) Station address setting Station address can be set as shown in the table below using the DIP switch 1 to 5 (SW). The bit 5 of SW specifies the number of 10s while the bit 1 to 4 of SW specifies the number of units. Do not change the setting while the power is being supplied. 5 SW 3 Station address 2 1 OFF OFF OFF OFF OFF OFF OFF OFF OFF ON Do not set. 1 (01H): Default setting OFF OFF OFF OFF OFF OFF ON ON OFF ON 2 (02H) 3 (03H) to OFF ON ON ON ON to 15 (0FH) ON ON OFF OFF OFF OFF OFF OFF OFF ON 16 (10H) 17 (11H) ON ON OFF OFF OFF OFF ON ON OFF ON 18 (12H) 19 (13H) ON to Do not set. to ON 44 4 ON ON ON