ANSI/SIA CP-01 – 2010
SECTION 1 USER CAUSED FALSE ALARMS (to be performed on each partition of the UUT)
VALIDATION PROCEDURE
REFERENCE
VP 1 Panel Annunciation
4.2.1
•
Verify that the UUT has an output for an auxiliary annunciation device that will sound all
annunciations required by the standard.
•
Verify that the UUT has an output for remote annunciation devices that will sound progress
annunciation during Entry Delay and Exit Time.
EOT
EXIT TIME
4.2.2.1
VP 2 Exit Time
•
Verify that the UUT’s Exit Time is defaulted (for all entry/exit zones that have a unique default
settings) to 60 seconds.
•
Arm the UUT.
•
Verify that the time between the last arming keystroke and a Full Arm (Exit Time) is 60
seconds.
•
Disarm the UUT.
•
•
Program the Exit Time to 45 seconds, and verify that the Exit Time is 45 seconds.
•
Program the Exit Time to 120 seconds, and verify that the Exit Time is 120 seconds.
•
Program the Exit Time to 256 seconds, and verify that the Exit Time is 255 seconds or less.
(Note: If the UUT did not accept programming to 256 seconds, proceed to the next test.)
•
Return the UUT to the default Exit Time setting.
•
Arm the UUT.
•
Trip an entry/exit zone.
•
Verify that the time between the last arming keystroke and the local alarm is 60 seconds.
•
Disarm the UUT.
If the UUT has a silent exit feature:
•
Arm the UUT with the silent feature, and verify that the Exit Time is 120 seconds.
•
Arm the UUT normally, and verify that the Exit Time is 60 seconds.
EOT