ANSI/SIA CP-01 – 2010
VALIDATION PROCEDURE
REFERENCE
VP 29 Call Waiting
4.5
•
Program a CALL WAITING CANCEL dialing sequence.
Note: The dial sequence for call waiting cancel is typically <*70><pause> on a DTMF line, but may
vary depending on the region of the country. To test this feature, a DTMF test set may be
used to confirm that the control can dial <*> and all the digits on a standard DTMF
phone.
•
Arm the UUT, and wait till the Exit Time has expired.
•
Trip any zone, and wait till an alarm transmission is started.
•
Verify, by use of a standard dial verifier, that the call waiting cancel sequence was sent before
the dialed phone number.
•
When the UUT senses that a connection was not made, verify that an alternative dialing
method was employed.
•
Verify that a warning to installers, not to use the call waiting cancel feature inappropriately, is
provided with the UUT.
EOT
Page 40