Download Monicon Tech.
Transcript
Monicon Tech. GTR-56 『Frequency』Page ¾ Parameter Screen ¾ Parameter Item Over Frequency Parameter Parameter name Default Range Enable Enable Enable/ Disable Action Mode Shutdown Shutdown 66 Hz 60~72 Frequency Setting (60 Hz) Frequency Setting (50 Hz) Delay Time D e s c r i p t i o n Check means enable this function. Shut down the engine after condition meets the set up value. This Range will be difference according to system frequency. 55 Hz 50~60 2 Sec. 1~10 Delay Time. Under Frequency Parameter Parameter name Default Range Enable Enable Enable/ Disable Action Mode Indicate Frequency Setting (60 Hz) Frequency Setting (50 Hz) Ver.:MG56003E 54 Hz D e s c r i p t i o n Check means enable this function. Four kind action modes can be selected. Shut down, Trip, Alarm, Indicate. 48~59 This range will be limited according to system frequency. 45 Hz 40~50 21