Language Reference
Arguments:
XIN1
XIN2
EPS
Q
REAL
REAL
REAL
BOO
any real analog value
to test if XIN1 has exceeded XIN2+EPS
hysteresis value (must be greater than zero)
TRUE if XIN1 has exceeded XIN2+EPS and is not yet
below XIN2-EPS
Description:
Hysteresis on a real value for a high limit.
Example of timing diagram:
XIN2+EPS
XIN2
XIN2-EPS
XIN1
Q
LIM_ALRM
lim_alrm
H
X
L
EPS
Arguments:
H
X
L
EPS
QH
Q
QL
REAL
REAL
REAL
REAL
BOO
BOO
BOO
QH
Q
QL
high limit value
input: any real analog value
low limit value
hysteresis value (must be greater than zero)
"high" alarm: TRUE if X above high limit H
alarm output: TRUE if X out of limits
"low" alarm: TRUE if X below low limit L
Description:
Hysteresis on a real value for high and low limits.
An hysteresis is applied on high and low limits. The hysteresis delta used for either high or
low limit is one half of the EPS parameter. Below is an example of timing diagram: