4 Operation
4.5 Updating the operating system
4.5.2 XC-CPU202
The following description (firmware update) applies to version 2.4.13 and
higher (target firmware version).
The operating system of the XC-CPU202 is updated inside the XSOFTCODESYS-2 programming system.
Procedure:
▶
▶
Establish a serial connection via the Ethernet interface of the PC with the
XC202.
Information on this is provided in → Section 3.4.6, “Connect PC”,
page26 and → Chapter 6, “Connection set-up PC – XC200”, Page 70.
Go to the “PLC Configuration” window in XSOFT-CODESYS-2 and open
the “Firmware” tab.
Figure 27:“PLC configuration” window
▶
▶
▶
▶
Click on the “Start” button (under “Update operating system”).
Select the firmware file for the XC202 and click on the “Open” button.
Click on “Next” to start the Setup Wizard.
Select the “FTP installation” option and then click on “Next”.
Figure 28:“FTP installation” window
▶
Enter the PLC's IP address and click on “Next”.
Note: The default network setting will be: IP address: 192.168.119.202
Modular PLC XC-CPU201-…(-XV), XC-CPU202-…-XV 06/14 MN05003001Z-EN