8.3
Normal and Latched Coils
A coil is a discrete output value represented by a 0x reference number. Because
output values are updated in State RAM by the controller’s CPU, a coil may be
used internally in the logic program or externally via the Traffic Cop to a discrete
output module. Coils are either OFF or ON, depending on power flow in the logic
program. When a coil is ON, it may either pass power to a discrete output circuit
on the shop floor or change the state of an internal relay contact in state RAM.
There are two types of coils:
Normal Coil
A normal coil is turned OFF if power at the controller is removed.
Latched Coil
L
If a latched coil has been energized at the time of a controller power loss, the coil
will come back up in the same state for one scan once power has been restored.