Download Hardware Manual
Transcript
7.5.5. Digital Output 1 and 2 (Pin 6 and 7) 7.5.5.1 Specification Outputs 1 and 2 are used for switching the valve. When the valve is not used the outputs may be free configured and utilized by the user. DigOUT1 Pin [6] DigOUT2 Pin [7] AGND Pin [12] Circuit Open Collector (internal pull-up resistor 2k2 and diode to +5 VDC) Switching delay <3 µs Figure 7 – Digital output 1 and 2 7.5.5.2 Wiring Examples DigOUT “Drain” Maximum input voltage +36 VDC Maximum load current 50 mA Maximum voltage drop <1.0 V @ 50 mA neMESYS Manual – Electrical Interfaces 39