Download Operation Manual
Transcript
HMi Operator Interface January 2007 Festo PLC A. HMi factory settings Baud rate: 9600, 8, None, 1 Controller Station number: 0 (no PLC station number in protocol for this PLC) Control area/state area: R0 / R10 Note: Connectable PLC: FEC-FC Model B. Definition of Controller Read/Write Address Table B-18: Festo PLC Registers Register Type WORD_DEVICE_IW WORD_DEVICE_OW WORD_DEVICE_FW WORD_DEVICE_TW WORD_DEVICE_CW WORD_DEVICE_R WORD_DEVICE_TP WORD_DEVICE_CP Format Iwn Own FWn TWn CWn Rn TPn CPn Word No. n: 0 – 255 n: 0 – 255 n: 0 – 9999 n: 0 – 255 n: 0 – 255 n: 0 – 255 n: 0 – 255 n: 0 – 255 Bit No. N/A N/A N/A N/A N/A N/A N/A N/A Data Size Word Word Word Word Word Word Word Word Table B-19: Festo PLC Contacts Register Type BIT_DEVICE_I BIT_DEVICE_O BIT_DEVICE_F BIT_DEVICE_T BIT_DEVICE_C BIT_DEVICE_TON BIT_DEVICE_TOFF ● Format In.b On.b Fn.b Tn Cn TONn TOFFn Word No. n: 0 – 255 n: 0 – 255 n: 0 – 9999 N/A N/A N/A N/A Bit No. b: 0 – 15 b: 0 – 15 b: 0 – 15 n: 0 – 255 n: 0 – 255 n: 0 – 255 n: 0 – 255 BIT_DEVICE_T / BIT_DEVICE_C / BIT_DEVICE_TON / BIT_DEVICE_TOFF: Only one bit can be changed at a time. C. Connections Note: 1. Communication port of the PLC: COM port 2. Use the dedicated cable for FESTO controllers and a cable for transferring TTL to RS-232, connect to the 6-pin RJ-12 connector at the PLC side. MN04802014E For more information visit: www.EatonElectrical.com B-23