Download ENGLISH
Transcript
CE LABELING AND RELEVANT DOCUMENTATION According to the requirements of the EN54-12 Standard, below we report the CE labelling along with the required information. 14 14 1293 1293 is a trademark of URMET S.p.A. Via Bologna, 188/C - 10154 Torino - Italy is a trademark of URMET S.p.A. Via Bologna, 188/C - 10154 Torino - Italy 14 14 1293-CPR-0406 DoP n. 1293-CPR-0406 1293-CPR-0407 DoP n. 1293-CPR-0407 FL100 FLR100 EN 54-12 Line detector using an optical light beam Fire safety EN 54-12 Line detector using an optical light beam Fire safety Documentation: see doc. LBT80777 Documentation: see doc. LBT80777 INSTALLATION The optical beam smoke detectors FLR100 and FL100 imply two different types of installation: FLR100 – Transmitter/receiver unit (Tx/Rx) + passive reflector This configuration involves a single FLR100, which operates simultaneously as transmitter and receiver (Tx/Rx), and a passive reflector placed at a distance from the Tx/Rx unit between 5 and 100 meters. The passive reflector must be chosen according to the distance from the FLR100 device: Distance Type of passive reflector 5 – 20 meters 10cm x 10cm 20 – 50 meters 20cm x 20cm 50 – 100 meters 30cm x 20cm FL100 – Separate transmitter unit (Tx) + receiver unit (Rx) This configuration involves two separate FL100 devices. One of them is configured as transmitter (Tx) and the other one as receiver (Rx). In this case, the transmitter (Tx) and the receiver (Rx) can be placed at a distance between 5 and 150 meters.