3.2.46 Point Type 80: Ethernet/USB Configuration Parameters (FloBoss 107)
Description:
Point type 80 provides Ethernet configuration parameters for the FloBoss 107.
Number of Logical Points:
2 configurable points may exist.
Table 3-51. Point Type 80, Ethernet/USB Configuration Parameters (FloBoss 107)
Point Type 80, Ethernet/USB Configuration Parameters (FloBoss 107)
Parameter#
Access
Data Type
Length
Range
Default
0
R/O
AC
12
N/A
Each unit is unique
1
R/W
AC
20
N/A
“10.0.0.2”
2
R/W
AC
20
N/A
“255.255.255.0”
3
R/W
AC
20
N/A
“10.0.0.1”
4
R/W
UINT16
2
0  655355
4000
5
R/O
UINT8
1
04
0
6
R/W
FL
4
0x
10.0
7
R/W
UINT8
1
01
0
8
R/O
UINT32
4
N/A
0
Description
Unique MAC address set by the factory.
IP address for this unit
Subnet address for this unit
Gateway address for this unit
ROC protocol port number
Number of active ROC protocol connections
ROC protocol timeout (in minutes). The connection closes
after this amount of time if no activity is detected.
Closes all ROC protocol connections. 1 = Close all
connections.
Not used in FloBoss 107.
Modbus protocol port number
9
R/W
UINT16
2
0  655355
502
10
R/O
UINT8
1
04
0
11
R/W
FL
4
0x
10.0
12
R/W
UINT8
1
01
0
13
R/O
UINT32
4
N/A
0
14
R/W
UINT8
1
02
2
Selects which address (ROC address or Modbus over IP slave
access) Modbus over IP should use. Valid values are:
0 = Use ROC address
1 = User Modbus over IP Slave Address
2 = Use either ROC address or Modbus TCP Address
15
R/W
UINT8
1
0  255
-
Specifies the slave address for Modbus over IP
16
R/W
UINT8
1
1  255
3
Modbus Master TCP connection timeout (in seconds).
17
R/W
UINT8
1
1  255
3
Modbus Master TCP close timeout (in seconds).
18
R/W
UINT8
1
RESERVED
19
R/W
UINT8
1
RESERVED
Number of active Modbus protocol connections
Modbus protocol timeout (in minutes). The connection closes
after this amount of time if no activity is detected.
Closes all Modbus protocol connections. 1 = Close all
connections.
Not used in FloBoss 107. .
Master Table 1 Block
3-164
Parameter Lists for Point Types
Revised June-2015