Download User`s Manual - Culinaire Systems
Transcript
30 E-Clipse Bypass Configurations for ACH550 Drives Smoke Control (Override1) Parameter Number 1602 1603 1604 1605 * Installation Parameters Changed Relative to HVAC Default Description Damper End Switch RUN ENABLE (Run Permissive) High Pressure Switch, High Priority Safeties START EN 1 (Safety Interlock 1) Supply Smoke Detector, Emergency Shutdown START EN 2 (Safety Interlock 2) Freezestat, Low Priority Safeties START EN 3 (Safety Interlock 3) Setting DI2 DI3 DI4 DI5 Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Automatic Smoke Control mode. Refer to the Smoke Control (Override1) documentation.