TROUBLESHOOTING Loop break alarm turns on even though the actuator operates normally. Loop break alarm turns on even though the actuator is operating normally. Is the loop break alarm time too short? (*1) YES Set the loop break alarm time to a suitable value. NO Is the loop break alarm span too great? (*2) YES Set the loop break alarm span to a suitable value. NO Call IDEC for assistance. END *1: Loop break alarm time may be too short compared to the loop break alarm span. *2: Loop break alarm span may be too great compared to the loop break alarm time. Note: Loop break alarm time and loop break alarm span Set the loop break alarm span to a value around 1.25 times bigger than the operation span in normal operation. Example: Heater in which temperature rises 150°C in 30 minutes When the loop break alarm time is 10 minutes, the operation span in normal operation is 50°C (150°C/30 minutes × 10 minutes). Set the loop break alarm span to 65°C which is about 1.25 times bigger than 50°C. Program control is terminated earlier than the configured time. Program control is terminated earlier than the configured time. Is PV start (*1) or PVR start (*1) selected as “program control mode start type“? YES Select SP start (*1) as “program control mode start type“. NO Is each step time suitable? NO Set each step time to a suitable value. YES Call IDEC for assistance. END *1: For program control mode start type, see page 6-41. 9-6 FC5A MicroSmart PID Module User’s Manual FC9Y-B1283