REHABILITATE CAUDELL HALL BUILDING 18 STATE UNIVERSITY OF NEW YORK BUFFALO STATE COLLEGE SUCF PROJECT NO. 03421 3.03 3.04 DIVISION 23 – HVAC GENERAL SYSTEM DESCRIPTION A. Provide normally open hot water coil valves. B. Provide normally open return air damper, normally closed relief air and normally closed outside air dampers and operators. C. Mode of operation (occupied/unoccupied) including building warm-up and pull-down cycles, as well as all system functions shall be programmable and controlled by the DDC system. D. Shutdown of air handling units and fans due to a fire alarm shall be by Division 26. The fire alarm system will send a signal to the DDC system for monitoring purposes only. The DDC system will provide a staggered restart of the units once the alarm is cleared. E. All setpoints shall be adjustable. WIRING A. Unless noted otherwise, all electrical wiring required to interconnect the components of the control system shall be furnished and installed by the controls system installer. Perform all wiring in accordance with the requirements listed below, code requirements and Division 26. B. Communication wiring shall be installed using the particular system recommended, plenum rated, jacket shielded cable. The communication network wiring shall be clearly marked with a specific color code. Communication wiring shall not be installed near noise producing equipment, such as ballasts, magnetic starters, etc. Communication wiring shall comply with the optimum requirements necessary to assure communication integrity and speed. C. All analog inputs and analog outputs shall be wired using 18 gauge stranded shielded cable. D. All digital outputs shall be wired using 18 gauge stranded wire. E. All wiring in mechanical rooms, walls shall be installed in EMT conduit. Concealed conduit and wiring is required in all finished spaces. F. Power Supplies: G. 1. Transformers – Each w/ low voltage fuse holder/disconnect. 2. Actuators and relays shall use separate transformers from those powering microprocessor control panels. 3. Transformers shall be sized for a minimum of 150% of the connected load. Convenience Outlet: 1. 110vac combination outlet w/ switch to kill 110vac to panel. 2. Switched 110vac to panel is fused before transformers (after outlet). TEMPERATURE CONTROLS 230923 - 25