Unit Controller Operation Additional compressors can be started when Evaporator LWT is higher than the Stage Up Temperature and the Stage Up Delay is not active. When multiple compressors are running, one should shut down if evaporator LWT is lower than the Stage Down Temperature and the Stage Down Delay is not active. All running compressors should shut down when the evaporator LWT is lower than the Shut Down Temperature. Stage Up Delay A minimum amount of time, defined by the Stage Up Delay set point, should pass between increases in the capacity stage. This delay should only apply when at least one compressor is running. If the first compressor starts and quickly shuts off for some reason, another compressor may start without this minimum time passing. Stage Down Delay compressor on each circuit shall be left on until each circuit has only one compressor running. Next To Start If both circuits have an equal number of compressors running or a circuit has no compressors available to start: • the available compressor with the least starts will be next to start • if starts are equal, the one with the least run hours will be next to start • if run hours are equal, the lowest numbered one will be next to start If the circuits have an unequal number of compressors running, the next compressor to start will be on the circuit with the least compressors running if it has at least one compressor available to start. Within that circuit: • the available compressor with the least starts will be next to start A minimum amount of time, defined by the Stage Down Delay set point, should pass between decreases in the capacity stage. This delay should not apply when the LWT drops below the Shut Down Temperature (unit should immediately shut down). • if starts are equal, the one with the least run hours will be next to start Compressor Staging in Ice Mode • if run hours are equal, the lowest numbered one will be next to start The first compressor on the unit should be started when evaporator LWT is higher than the Startup Temperature. Next to Stop Additional compressors should be started as quickly as possible with respect to the Stage Up Delay. • the running compressor with the most run hours will be next to stop The unit should shut down when evaporator LWT is less than the LWT target. • if run hours are equal, the one with the least starts will be next to stop Stage Up Delay • if starts are equal, the lowest numbered one will be next to stop A fixed stage up delay of one minute between compressor starts should be used in this mode. Staging Sequence If both circuits have an equal number of compressors running: If the circuits have an unequal number of compressors running, the next compressor to stop will be on the circuit with the most compressors running. Within that circuit: This section defines which compressor is the next one to start or stop. In general, compressors with fewer starts will normally start first, and compressors with more run hours will normally stop first. • the running compressor with the most run hours will be next to stop If possible circuits will be balanced in stage. If a circuit is unavailable for any reason, the other circuit shall be allowed to stage all compressors on. When staging down, one • if starts are equal, the lowest numbered one will be next to stop IOM 1206-1 • if run hours are equal, the one with the least starts will be next to stop 35